IMPORTANT WEBSITE UPDATE! We now show LIVE stock levels and allow Trade Account customers to see their pricing and place orders directly on their account. Trade Customers, please call or email us to get your users setup with access.

Your one stop-shop for fuel & tanker equipment
Next day delivery available

DAY TANK CONTROLLER - Modular Duty/Standby Controllers for diesel generator day tank pump and valve control with BMS outputs

Stock Code: PAELDXXXX

Minimum Quantity:

From ex VAT (%) VAT n/a
From inc VAT (%) VAT n/a
Call Free
Discount:
Price ex VAT (%):
Price inc VAT (%):
VAT n/a:

The PFS Fueltec Duty Standby Pump Control Panel is a modular microprocessor-controlled system designed for managing duty, standby, and assist operations in twin pumpsets. This panel is specifically engineered for transferring fuel from a bulk tank to a day tank, incorporating advanced features such as tank level controls, valve control, bund/seal leakage detection, and interfaces for BMS and fire systems. The innovative modular construction ensures flexibility and ease of customization, making it a reliable and efficient choice for various applications.

Typical Applications

  • Duty/Standby/Assist Pumpsets: Compatible with pumpsets from any manufacturer.
  • Diesel Fuel Transfer Sets: Extensively used with our diesel fuel transfer sets.

Optional Extras

  • Additional Volt-Free Contacts: For external equipment integration.
  • Internal RCDs: Interlocked with pump changeover, with an alarm for pump failure.
  • Remote Dialler: For critical systems, sends text messages to your mobile phone.
  • Run Time Counter: Monitors pump usage.
  • Door Mount Ammeter: For easy current monitoring.
  • Additional Interface Board: With the following functions:
    1. Day tank High High
    2. Day tank Low Low
    3. Bulk tank Low
    4. Bulk tank Low Low
    5. Pump 2 Fail (Overload or input from external flow switch)
    6. Emergency Stop
    7. Bund Alarm
    8. Fire Cut-off
    9. Pump 1 Fail (Overload or input from external flow switch)
    10. Flow switch
    11. Pump 1 run
    12. Pump 2 run

Please specify required outputs when ordering as a separate relay with volt-free contacts will be fitted for each required output.

Key Features

  • Competitive Pricing: Significantly more cost-effective compared to traditional control panels still offered by many manufacturers.
  • Enhanced Reliability: Utilizes a microprocessor and printed circuit board (PCB) for superior performance and reliability.
  • Modular Design: Easily customizable for specific requirements, allowing for fast delivery times, with some units held in stock.
  • Comprehensive Standard Features: A wide array of features included as standard (see details below).
  • Versatile Voltage Options: Typically single-phase control panel, with versions available in 12V, 24V, 110V, and 400/415V 3 phase.
  • Cost-Effective Optional Extras: Due to the market-leading modular design, optional extras are inexpensive.
  • Custom Branding: For resellers, we offer custom branding on the fascia at no extra cost.
  • Proven Track Record: Over a thousand units in use, often customized with customer branding.
  • GSM Module Option: Our twin pump controller can send status updates via text message (optional feature).
  • UK Manufactured: Proudly manufactured in-house by Pump Engineering.


Standard Features

  1. Compact Microprocessor Panel: Self-contained with plug-in connections for easy installation.
  2. Automatic Pump Changeover: Alternating starting sequence ensures even wear and reliable operation.
  3. Control Modes: Auto/off/manual facility available for each pump.
  4. Bulk Tank Level Controls: Includes low/low pump protection with local LED, sounder indication, and remote alarm signal.
  5. Day Tank Level Controls: High and low level alarms with local LED, sounder indication, and remote alarm signal.
  6. Building Management Interface (BMS): Integration with fire cut-off for enhanced safety.
  7. Standard Voltage: 240/1/50, with options for 415/3/50, 110/1/50, 24/1/50, and 12/1/50.
  8. Epoxy-Coated Steel Enclosure: Durable construction, measuring 400mm x 500mm x 150mm.
  9. Standard BMS Outputs: “Commoned” to two relays:
    • Relay 3:
      • Bulk low low
      • Day high high
      • Fire
      • Bund leak/full
      • Emergency stop active
    • Relay 4:
      • Bulk low
      • Day low low
      • Pump 1 tripped
      • Pump 2 tripped
      • In manual, both pumps off will sound local panel alarm only (maintenance).

We have placed cookies on your device to help make this website better.

Your Basket
Subtotal
Delivery() No shipping method available Delivery
Call
Discount
VAT
Total (inc VAT)
Total (ex VAT)

Your order contains no items