Close
Your one stop-shop for fuel & tanker equipment
Next day delivery available

DAY TANK CONTROLLER - Modular Duty/Standby Controllers for diesel generator day tank pump and valve control with BMS outputs

Monitoring & Control

Stock Code: PAELDXXXX

Call

The PFS Fueltec Duty Standby Pump Control Panel is a modular microprocessor-controlled system designed for managing duty, standby, and assist operations in twin pumpsets. This panel is specifically engineered for transferring fuel from a bulk tank to a day tank, incorporating advanced features such as tank level controls, valve control, bund/seal leakage detection, and interfaces for BMS and fire systems. The innovative modular construction ensures flexibility and ease of customization, making it a reliable and efficient choice for various applications.

Typical Applications

  • Duty/Standby/Assist Pumpsets: Compatible with pumpsets from any manufacturer.
  • Diesel Fuel Transfer Sets: Extensively used with our diesel fuel transfer sets.

Optional Extras

  • Additional Volt-Free Contacts: For external equipment integration.
  • Internal RCDs: Interlocked with pump changeover, with an alarm for pump failure.
  • Remote Dialler: For critical systems, sends text messages to your mobile phone.
  • Run Time Counter: Monitors pump usage.
  • Door Mount Ammeter: For easy current monitoring.
  • Additional Interface Board: With the following functions:
    1. Day tank High High
    2. Day tank Low Low
    3. Bulk tank Low
    4. Bulk tank Low Low
    5. Pump 2 Fail (Overload or input from external flow switch)
    6. Emergency Stop
    7. Bund Alarm
    8. Fire Cut-off
    9. Pump 1 Fail (Overload or input from external flow switch)
    10. Flow switch
    11. Pump 1 run
    12. Pump 2 run

Please specify required outputs when ordering as a separate relay with volt-free contacts will be fitted for each required output.

Key Features

  • Competitive Pricing: Significantly more cost-effective compared to traditional control panels still offered by many manufacturers.
  • Enhanced Reliability: Utilizes a microprocessor and printed circuit board (PCB) for superior performance and reliability.
  • Modular Design: Easily customizable for specific requirements, allowing for fast delivery times, with some units held in stock.
  • Comprehensive Standard Features: A wide array of features included as standard (see details below).
  • Versatile Voltage Options: Typically single-phase control panel, with versions available in 12V, 24V, 110V, and 400/415V 3 phase.
  • Cost-Effective Optional Extras: Due to the market-leading modular design, optional extras are inexpensive.
  • Custom Branding: For resellers, we offer custom branding on the fascia at no extra cost.
  • Proven Track Record: Over a thousand units in use, often customized with customer branding.
  • GSM Module Option: Our twin pump controller can send status updates via text message (optional feature).
  • UK Manufactured: Proudly manufactured in-house by Pump Engineering.


Standard Features

  1. Compact Microprocessor Panel: Self-contained with plug-in connections for easy installation.
  2. Automatic Pump Changeover: Alternating starting sequence ensures even wear and reliable operation.
  3. Control Modes: Auto/off/manual facility available for each pump.
  4. Bulk Tank Level Controls: Includes low/low pump protection with local LED, sounder indication, and remote alarm signal.
  5. Day Tank Level Controls: High and low level alarms with local LED, sounder indication, and remote alarm signal.
  6. Building Management Interface (BMS): Integration with fire cut-off for enhanced safety.
  7. Standard Voltage: 240/1/50, with options for 415/3/50, 110/1/50, 24/1/50, and 12/1/50.
  8. Epoxy-Coated Steel Enclosure: Durable construction, measuring 400mm x 500mm x 150mm.
  9. Standard BMS Outputs: “Commoned” to two relays:
    • Relay 3:
      • Bulk low low
      • Day high high
      • Fire
      • Bund leak/full
      • Emergency stop active
    • Relay 4:
      • Bulk low
      • Day low low
      • Pump 1 tripped
      • Pump 2 tripped
      • In manual, both pumps off will sound local panel alarm only (maintenance).